AI Search

Tell us in one sentence about your application or question to search related products, technical articles and calculators.

03 / Stainless-steel cable entry

Stainless Steel Cable Glands

Stainless-steel cable glands hold the cable and seal the enclosure opening. Choose a standard gland for a plain cable entry, or an EMC or armoured construction to suit the cable. The steel grade and seal material must suit the chemicals and cleaning conditions at the installation.

  • Required stainless-steel grade
  • Cable and thread dimensions
  • Corrosion and cleaning exposure

Cable gland families

Compare cable glands by material, cable construction and duty.

Choose nylon, brass or stainless steel by body material, or compare EMC, armoured, hazardous-area, marine and conduit-entry designs by the job they must perform.

Stainless Steel Cable Glands range

Choose your stainless steel cable glands

Stainless-steel glands for sealed cable entries on outdoor and process equipment.

Choose one product or compare the full family

Models & dimensions

Stainless Steel Cable Glands: specifications and dimensions

Select a product to see its specifications, drawings and sizes.

Stainless Steel Cable Glands

Which fitting do you need?

Choose a product above, or show all products to compare sizes and construction.
  • 01Cable and seal range
  • 02Entry thread and dimensions
  • 03Material and installation duty
Stainless-Steel Cable Gland — Metric, PG, G and NPT

01 / Stainless-steel cable entry

Stainless-Steel Cable Gland — Metric, PG, G and NPT

A stainless-steel cable gland for straight cable entry, with Metric, PG, G and NPT thread series.

Product reference

Construction
Standard Stainless Steel Glands
Application
A straight cable entry calls for a stainless-steel gland body.

Key specifications

Body Material
Stainless steel (304 or 316L)
Thread Systems
Metric, PG, G and NPT
Metric model series
SSM
PG model series
SSPG

Product specifications

Construction and details

Stainless-Steel Cable Gland — Metric, PG, G and NPT — Separated assembly components
Stainless-Steel Cable Gland — Metric, PG, G and NPT

Separated assembly components

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

Further specifications
G model series
SSG
NPT model series
SSNPT
Seal Material
EPDM or silicone rubber
Clamping insert
Nylon PA66
O-ring material
EPDM or silicone rubber
Ingress protection
IP68, 10 bar
Static temperature
−40°C to +100°C; short term to +120°C
Dynamic temperature
−20°C to +80°C; short term to +100°C
Claw material flammability
UL 94 V-2 (PA66)
Key features
  • Stainless-steel bodyThe gland provides a metal cable-entry connection in stainless steel.
  • Four entry-thread systemsThe range includes Metric, PG, G and NPT versions.
304 Stainless Steel Waterproof Breathable Cable Gland

02 / Stainless-steel cable entry

304 Stainless Steel Waterproof Breathable Cable Gland

Seal and retain a cable while allowing the enclosure to breathe through a separate vent.

Product reference

Construction
Breathable Stainless Steel Cable Glands
Application
Cable entry with 304 stainless steel body and enclosure ventilation.

Key specifications

Product Type
Stainless steel breathable cable gland
Body material
304 stainless steel
Protection rating
IP68
Entry threads
M10×1.5 to M25×1.5

Product specifications

Construction and details

Further specifications
Cable diameter
3–16 mm, depending on size
Key features
  • Cable sealing and ventingThe cable seal and breathing path serve separate functions.
  • Metric size optionsChoose the thread and cable sealing range together.
M-NW Female-Thread Cable Gland for Threaded Conduit

03 / Stainless-steel cable entry

M-NW Female-Thread Cable Gland for Threaded Conduit

An M-NW-series metal cable gland with a female-thread connection for a threaded conduit or mating entry.

Product reference

Construction
Standard Stainless Steel Glands
Application
A cable gland must join a male-threaded conduit or fitting through an internal-thread connection.

Key specifications

Product Type
Female Thread Cable Gland / Conduit to Cable Fitting
Body Material
Nickel-Plated Brass, Stainless Steel (304/316L)
Claw
Nylon (PA)
Seal & O-Ring
NBR

Product specifications

Construction and details

Further specifications
Protection Rating
IP68 – 10 Bar
Static Temperature
-40°C to 100°C (short term to 120°C)
Dynamic Temperature
-20°C to 80°C (short term to 100°C)
Thread Types
Female-thread connection; thread standard and size depend on the model
Key features
  • Female-thread connectionThe internal thread connects to a male-threaded mating part.
  • M-NW model codesThe M-NW dimension series identifies the model and cable sealing range.
  • NBR sealing partsThe construction combines an NBR seal and O-ring with a nylon claw.
M-NLW Internal-Thread Cable Gland

04 / Stainless-steel cable entry

M-NLW Internal-Thread Cable Gland

An M-NLW-series metal cable gland with an internal thread for connection to a male-threaded entry.

Product reference

Construction
Standard Stainless Steel Glands
Application
The equipment or adjoining fitting presents a male thread that needs a female-thread cable gland.

Key specifications

Product Type
Female Thread / Internal Thread Cable Gland
Body Material
Nickel-Plated Brass, Stainless Steel (304/316L)
Claw
Nylon (PA)
Seal & O-Ring
NBR (Nitrile Rubber)

Product specifications

Construction and details

Further specifications
Protection Rating
IP68 – 10 Bar
Static Temperature
-40°C to 100°C (short term to 120°C)
Dynamic Temperature
-20°C to 80°C (short term to 100°C)
Thread Types
Metric, PG, G, NPT (Internal/Female Thread)
Key features
  • Internal entry threadThe gland connects to a male-threaded mating entry.
  • M-NLW dimension seriesM-NLW codes identify this construction and its cable-range options.
  • NBR seal and O-ringNitrile-rubber sealing parts work with the nylon clamping claw.
M-LBK Double-Flare Cable Gland

05 / Stainless-steel cable entry

M-LBK Double-Flare Cable Gland

An M-LBK-series metal cable gland with a double-flare cable-entry shape and NBR/PA6 sealing components.

Product reference

Construction
Standard Stainless Steel Glands
Application
The installation drawing calls for the double-flare M-LBK construction.

Key specifications

Design
Double Flare / Double Trumpet Mouth
Body Material
Nickel-Plated Brass, Stainless Steel (304, 316)
Seal Material
NBR (Nitrile Rubber), PA6 Nylon
Protection Rating
IP68 – 10 Bar

Product specifications

Construction and details

Further specifications
Static Temperature
-40°C to 100°C (short term to 120°C)
Dynamic Temperature
-20°C to 80°C (short term to 100°C)
Key features
  • Double-flare shapeThe construction uses a double trumpet-mouth form at the cable entry.
  • Metal body optionsThe range includes nickel-plated brass and stainless-steel body options.
  • M-LBK model codesThe model schedule links the M-LBK code to thread, cable range and fitting dimensions.
MG-Series EMC Cable Gland

06 / Stainless-steel cable entry

MG-Series EMC Cable Gland

An MG-series EMC cable gland that combines cable clamping and sealing with contact to the cable screen.

Product reference

Construction
Stainless Steel EMC Glands
Application
A screened cable enters an enclosure and its screen needs a connection through an MG gland.

Key specifications

Product Type
MG Series EMC Shielding Cable Gland
Body Material
Nickel-Plated Brass, Stainless Steel (304, 316L)
Claw
Nylon (PA66)
Seal & O-Ring
EPDM Rubber (Custom options available)

Product specifications

Construction and details

MG-Series EMC Cable Gland — Shield-contact assembly
MG-Series EMC Cable Gland

Shield-contact assembly

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

Confirm the mating interface, contact arrangement and mounting dimensions for the selected model.

Further specifications
Protection Rating
IP68 – 10 Bar
Static Temperature
-40°C to 100°C (short term to 120°C)
Dynamic Temperature
-20°C to 80°C (short term to 100°C)
Thread Types
Metric, PG, G(PF/BSP), NPT
Function
Cable-screen contact and cable retention
Seals for E.M25A-EMC / E.M32B-EMC
EPDM or silicone rubber
E.M25A-EMC / E.M32B-EMC claw flammability
UL 94 V-2 (PA66)
Key features
  • Screen contactThe gland includes a path for contacting the cable braid or screen at the entry.
  • EPDM sealing partsThe MG EMC construction uses an EPDM seal and O-ring with a PA66 claw.
  • Metal body choicesNickel-plated brass and stainless-steel versions are available.
Spring-Contact EMC Cable Gland

07 / Stainless-steel cable entry

Spring-Contact EMC Cable Gland

An EMC cable gland with a contact spring that connects the cable screen to the metal gland body.

Product reference

Construction
Stainless Steel EMC Glands
Application
A screened cable needs a spring-contact termination at the enclosure entry.

Key specifications

Product Type
Spring-Type EMC Shielding Cable Gland
Body & Nut Material
Nickel-Plated Brass, Stainless Steel (304, 316)
Contact Spring
Conductive spring; material depends on the model
Clamping Insert
Polyamide (PA6 V2)

Product specifications

Construction and details

Further specifications
Seal & O-Ring
NBR (Nitrile Rubber)
Protection Rating
IP68 – 5 Bar
Operating Temperature
-40°C to +100°C (short term to +120°C)
Thread Types
Metric (EN 60423), PG
Function
Cable-screen contact
Key features
  • Contact springA conductive spring forms the screen-contact element.
  • NBR sealing partsThe seal and O-ring are NBR, with a PA6 clamping insert.
  • Metric and PG entriesThe range includes Metric and PG enclosure threads.
D-Series EMC Cable Gland

08 / Stainless-steel cable entry

D-Series EMC Cable Gland

A D-series EMC cable gland with a metal body, polyamide claw and NBR sealing parts for screened cable entries.

Product reference

Construction
Stainless Steel EMC Glands
Application
Connect a cable screen at the enclosure entry with an NBR seal around the cable jacket.

Key specifications

Product Series
D Series EMC Cable Gland
Body Material
Nickel-Plated Brass, Stainless Steel (304, 316L)
Claw
Nylon (PA)
Seal & O-Ring
NBR (Nitrile Rubber) (Custom options available)

Product specifications

Construction and details

D-Series EMC Cable Gland — Shield-contact assembly
D-Series EMC Cable Gland

Shield-contact assembly

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

Confirm the mating interface, contact arrangement and mounting dimensions for the selected model.

Further specifications
Protection Rating
IP68 – 10 Bar
Static Temperature
-40°C to 100°C (short term to 120°C)
Dynamic Temperature
-20°C to 80°C (short term to 100°C)
Function
Cable-screen contact and cable retention
Key features
  • D-series constructionThe D-series gland combines screen contact with cable clamping at the enclosure entry.
  • NBR sealing partsThe standard seal and O-ring are NBR, with other seal options available for some models.
  • Metal body optionsThe range includes nickel-plated brass and stainless-steel bodies.
F-Series EMC Cable Gland for Metric Entries

09 / Stainless-steel cable entry

F-Series EMC Cable Gland for Metric Entries

An F-series EMC cable gland with a metal body, nylon fastening parts and an NBR seal for Metric entries.

Product reference

Construction
Stainless Steel EMC Glands
Application
A screened-cable installation calls for an F-series gland with a Metric enclosure thread.

Key specifications

Product Series
F Series EMC Cable Gland
Body & Nut Material
Nickel-Plated Brass or Stainless Steel
Fastener
Nylon / Plastic
Seal & O-Ring
NBR (Nitrile Rubber)

Product specifications

Construction and details

Further specifications
Protection Rating
IP68 – 10 Bar
Operating Temperature
-40°C to +100°C (short term to 120°C)
Thread Type
Metric
Function
Cable-screen contact and cable retention
Key features
  • Metric entryThis F-series construction uses a Metric threaded connection.
  • Metal body and nylon partsThe body is brass or stainless steel with nylon fastening components.
  • NBR sealing partsNitrile rubber forms the seal and O-ring around the cable-entry assembly.
Ex-VI Clamping Gland for Unarmoured Cable

10 / Stainless-steel cable entry

Ex-VI Clamping Gland for Unarmoured Cable

An Ex-VI metal clamping gland for unarmoured cable, with NBR or silicone sealing parts.

Product reference

Construction
Stainless Ex Non-Armoured Glands
Application
An unarmoured cable needs an Ex-VI clamping gland at a threaded equipment entry.

Key specifications

Product Type
Clamping gland for unarmoured cable
Model
Ex-VI
Body Material
Nickel-plated brass, SS304 stainless steel, or SS316 stainless steel
Seal Material
NBR or Silicone

Product specifications

Construction and details

Ex-VI Clamping Gland for Unarmoured Cable — Separated assembly components
Ex-VI Clamping Gland for Unarmoured Cable

Separated assembly components

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

This illustration does not establish the current model’s certification or approval.

Ex-VI Clamping Gland for Unarmoured Cable — Section view and dimension markers
Ex-VI Clamping Gland for Unarmoured Cable

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: AG · H · GL

Model specification tables
Further specifications
Ingress Protection
IP66
Operating Temperature
-60°C to +100°C
Applicable Cable
Non-Armoured Cables
Key features
  • Cable-clamping constructionEx-VI retains the unarmoured cable within the metal body.
  • Two seal optionsThe sealing arrangement uses NBR or silicone, depending on the configuration.
  • Entry threadsMetric, NPT and G versions are included in this construction.
Ex-VIG Clamping Gland for Unarmoured Cable

11 / Stainless-steel cable entry

Ex-VIG Clamping Gland for Unarmoured Cable

An Ex-VIG clamping gland for unarmoured cable, offered in nickel-plated brass and stainless-steel body configurations.

Product reference

Construction
Stainless Ex Non-Armoured Glands
Application
A clamping gland with a nickel-plated brass or stainless steel body.

Key specifications

Product Type
Clamping gland for unarmoured cable
Model
BDM-VIG / Ex-VIG
Body Material
Nickel-Plated Brass / Stainless Steel (304, 316)
Seal Material
NBR or Silicone

Product specifications

Construction and details

Ex-VIG Clamping Gland for Unarmoured Cable — Separated assembly components
Ex-VIG Clamping Gland for Unarmoured Cable

Separated assembly components

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

This illustration does not establish the current model’s certification or approval.

Ex-VIG Clamping Gland for Unarmoured Cable — Section view and dimension markers
Ex-VIG Clamping Gland for Unarmoured Cable

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: AG · H · GL

Model specification tables
Further specifications
Ingress Protection
IP66
Operating Temperature
-60°C to +100°C
Applicable Cable
Non-Armoured Cables
Key features
  • Ex-VIG model identityBDM-VIG and Ex-VIG identify this unarmoured-cable clamping construction.
  • Body-material choicesThe range includes nickel-plated brass, 304 stainless steel and 316 stainless steel.
  • Elastomer seal choicesNBR and silicone sealing options are available.
Ex-VIIIG Single-Seal Armoured Cable Gland

12 / Stainless-steel cable entry

Ex-VIIIG Single-Seal Armoured Cable Gland

An Ex-VIIIG gland combining single sealing and armour clamping for wire-, braid- or tape-armoured cable.

Product reference

Construction
Stainless Ex Armoured Glands
Application
An armoured cable requires the Ex-VIIIG single-seal construction.

Key specifications

Product Type
Single-seal armoured cable gland
Model
Ex-VIIIG / BDM-VIIIG
Body Material
Nickel-Plated Brass / Stainless Steel (304, 316)
Seal Material
Silicone Rubber

Product specifications

Construction and details

Ex-VIIIG Single-Seal Armoured Cable Gland — Separated assembly components
Ex-VIIIG Single-Seal Armoured Cable Gland

Separated assembly components

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

This illustration does not establish the current model’s certification or approval.

Ex-VIIIG Single-Seal Armoured Cable Gland — Section view and dimension markers
Ex-VIIIG Single-Seal Armoured Cable Gland

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: AG · GL

Model specification tables
Further specifications
Ingress Protection
IP66
Operating Temperature
-60°C to +100°C
Applicable Cable
Steel Wire, Braided, and Steel Tape Armoured Cables
Key features
  • Single sealing with armour clampingThe Ex-VIIIG form combines one sealing arrangement with mechanical armour retention.
  • Silicone sealsThe sealing components use silicone rubber.
  • Metal body choicesNickel-plated brass and 304 or 316 stainless-steel versions are available.
Ex-VIIG Double-Seal Armoured Cable Gland

13 / Stainless-steel cable entry

Ex-VIIG Double-Seal Armoured Cable Gland

An Ex-VIIG metal cable gland with double sealing and an armour-clamping system.

Product reference

Construction
Stainless Ex Armoured Glands
Application
An armoured cable entry requires the Ex-VIIG double-seal arrangement.

Key specifications

Product Type
Double-seal armoured cable gland
Model
Ex-VIIG / BDM-VIIG
Body Material
Nickel-Plated Brass / Stainless Steel (304, 316)
Seal Material
Silicone Rubber

Product specifications

Construction and details

Ex-VIIG Double-Seal Armoured Cable Gland — Separated assembly components
Ex-VIIG Double-Seal Armoured Cable Gland

Separated assembly components

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

This illustration does not establish the current model’s certification or approval.

Ex-VIIG Double-Seal Armoured Cable Gland — Section view and dimension markers
Ex-VIIG Double-Seal Armoured Cable Gland

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: AG · GL

Model specification tables
Further specifications
Ingress Protection
IP66
Operating Temperature
-60°C to +100°C
Applicable Cable
Steel Wire, Braided, and Steel Tape Armoured Cables
Key features
  • Double-seal arrangementTwo sealing stages accompany the armour-clamping system.
  • Silicone sealing partsThe gland uses silicone seals.
  • Brass and stainless optionsThe range includes nickel-plated brass and 304 or 316 stainless-steel bodies.
Ex-BG Clamping Gland for Unarmoured Cable

14 / Stainless-steel cable entry

Ex-BG Clamping Gland for Unarmoured Cable

An Ex-BG metal clamping gland for unarmoured cable, with NBR, PTFE or silicone sealing options and Metric, NPT or G entries.

Product reference

Construction
Stainless Ex Non-Armoured Glands
Application
An unarmoured cable entry needs NBR, PTFE or silicone seal options with a Metric, NPT or G connection.

Key specifications

Product Type
Clamping gland for unarmoured cable
Model
BDM-BG / Ex-BG
Body Material
Nickel-Plated Brass / Stainless Steel
Seal Material
NBR, PTFE, or Silicone

Product specifications

Construction and details

Ex-BG Clamping Gland for Unarmoured Cable — Section view and dimension markers
Ex-BG Clamping Gland for Unarmoured Cable

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: AG · GL

Model specification tables
Ex-BG Clamping Gland for Unarmoured Cable — Separated assembly components
Ex-BG Clamping Gland for Unarmoured Cable

Separated assembly components

Compare the arrangement of the illustrated parts. Confirm the assembly instructions for the selected model.

This illustration does not establish the current model’s certification or approval.

Further specifications
Ingress Protection
IP66
Operating Temperature
-40°C to +100°C
Applicable Cable
Non-Armoured Cables
Key features
  • Unarmoured-cable clampEx-BG retains the cable without an armour-clamping assembly.
  • Three seal-material optionsNBR, PTFE and silicone are available as configuration options.
  • Three entry-thread systemsMetric, NPT and G versions serve different equipment entries.
BDM-BDT / Ex-BDT Threaded Stopping Plug

15 / Stainless-steel cable entry

BDM-BDT / Ex-BDT Threaded Stopping Plug

A BDM-BDT / Ex-BDT metal stopping plug for closing an unused threaded enclosure opening.

Product reference

Construction
Stainless Ex Thread Accessories
Application
A threaded enclosure entry is unused and needs a solid closure.

Key specifications

Product Type
Threaded stopping plug / blanking plug
Model
BDM-BDT / Ex-BDT
Body Material
Nickel-Plated Brass / Stainless Steel (304, 316)
Seal Material
NBR, PTFE or silicone

Product specifications

Construction and details

BDM-BDT / Ex-BDT Threaded Stopping Plug — Section view and dimension markers
BDM-BDT / Ex-BDT Threaded Stopping Plug

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: H · GL · AG

Model specification tables
Further specifications
Ingress Protection
IP66
Operating Temperature
-60°C to +100°C
Key features
  • Solid threaded closureThe plug closes an opening without passing a cable through it.
  • Metal body optionsNickel-plated brass and 304 or 316 stainless-steel versions are available.
BGJ-A Female-to-Female Pipe Coupler

16 / Stainless-steel cable entry

BGJ-A Female-to-Female Pipe Coupler

A BGJ-A metal pipe coupler with female threads at both ends for joining threaded connections.

Product reference

Construction
Stainless Ex Thread Accessories
Application
Two male-threaded connections need a female-to-female coupler.

Key specifications

Product Type
Female-to-female pipe coupler / reducer
Model
BGJ-A
Body Material
Nickel-Plated Brass / Stainless Steel
Thread 1 (Female)
G (BSP) (Standard); M, NPT (Custom)

Product specifications

Construction and details

BGJ-A Female-to-Female Pipe Coupler — Section view and dimension markers
BGJ-A Female-to-Female Pipe Coupler

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: L

Model specification tables
Further specifications
Thread 2 (Female)
G (BSP) (Standard); M, NPT (Custom)
Ingress Protection
IP65
Key features
  • Two female-thread endsThe coupler joins male-threaded mating components.
  • Straight or reducing formsBGJ-A includes straight and reducing connection forms.
  • Metal body optionsNickel-plated brass and stainless-steel versions are available.
BGJ-B Thread Adapter — Reducer and Enlarger

17 / Stainless-steel cable entry

BGJ-B Thread Adapter — Reducer and Enlarger

A BGJ-B metal thread adapter for changing the connection size at a threaded entry.

Product reference

Construction
Stainless Ex Thread Accessories
Application
The equipment entry and adjoining connection need different thread sizes.

Key specifications

Product type
Thread adapter — reducer or enlarger
Body material
Nickel-plated brass or stainless steel
Model series
BGJ-B

Product specifications

Construction and details

BGJ-B Thread Adapter — Reducer and Enlarger — Section view and dimension markers
BGJ-B Thread Adapter — Reducer and Enlarger

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: L · GL

Model specification tables
Key features
  • Reducer or enlarger functionThe adapter changes the threaded connection size.
  • Metric, NPT and G seriesThe BGJ-B model tables cover Metric, NPT and G dimensional series.
  • Metal constructionBrass and stainless-steel body options are available.
BGJ-C Male-to-Male Reducing Nipple

18 / Stainless-steel cable entry

BGJ-C Male-to-Male Reducing Nipple

A BGJ-C reducing nipple with male threads at both ends for joining female-threaded connections.

Product reference

Construction
Stainless Ex Thread Accessories
Application
Two female-threaded components need a male-to-male connecting nipple.

Key specifications

Connection
Male-to-male threaded connection
Body material
Nickel-plated brass or stainless steel
Model series
BGJ-C

Product specifications

Construction and details

BGJ-C Male-to-Male Reducing Nipple — Section view and dimension markers
BGJ-C Male-to-Male Reducing Nipple

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: L · GL

Model specification tables
Key features
  • Male threads at both endsThe nipple screws into two female-threaded mating connections.
  • Compact reducing connectionThe reducing form joins connections of different sizes.
  • Metric, NPT and G seriesThe dimensional range includes Metric, NPT and G model series.
BGJ-D Male-to-Female Reducing Bushing

19 / Stainless-steel cable entry

BGJ-D Male-to-Female Reducing Bushing

A BGJ-D reducing bushing with a larger male thread around a smaller female-threaded opening.

Product reference

Construction
Stainless Ex Thread Accessories
Application
A larger female-threaded entry needs to accept a smaller male-threaded component.

Key specifications

Connection
Larger male thread to smaller female thread
Body material
Nickel-plated brass or stainless steel
Model series
BGJ-D
Ingress protection
IP65

Product specifications

Construction and details

BGJ-D Male-to-Female Reducing Bushing — Section view and dimension markers
BGJ-D Male-to-Female Reducing Bushing

Section view and dimension markers

Read the marked dimensions with the current model drawing; do not infer sizes by measuring the illustration.

Drawing markers: L

Model specification tables
Key features
  • Male-to-female reductionThe outside male thread fits the larger opening; the inside female thread receives the smaller component.
  • Metric, NPT and G formsThe range includes reductions within Metric, NPT and G thread systems.

Model specification tables

Model sizes

Open a table to find the thread size, cable range and dimensions.
Stainless-Steel Cable Gland — Metric, PG, G and NPT

Stainless-steel cable entry

Stainless-Steel Cable Gland — Metric, PG, G and NPT

Model specificationsMetric thread
ModelEntry threadCable diameter range (mm)Thread length GL (mm)Thread outside diameter AG (mm)Length H (mm)Spanner size (mm)
SSM8M8×12-5681412
SSM10M10×13-6.57101714
SSM12M12×1.53-6.57121714/15
SSM12-8M12×1.54-88121718/15
SSM14-6M14×1.53-68141917
SSM14M14×1.54-88141918
SSM16M16×1.54-88161918
SSM16-10M16×1.55-108161920/18
SSM18M18×1.55-108181920
SSM18-12M18×1.56-128182222/20
SSM20M20×1.56-128202022
SSM20-12M20×1.510-148202324/22
SSM22M22×1.510-148222024
SSM22-16M22×1.512-168222327/24
SSM25-14M25×1.510-149252224/27
SSM25-16M25×1.512-169252227
SSM25-18M25×1.513-189252230
SSM27M27×1.513-189272230
SSM32-18M32×1.513-1810322935
SSM32M32×1.515-2210322535
SSM32-25M32×1.518-2510322840/35
SSM36-22M36×1.515-2210363140
SSM36M36×1.518-2510362840
SSM40-25M40×1.518-2510402840/45
SSM40-30M40×1.522-3010403045
SSM40-33M40×1.525-3310403050/45
SSM47M47×1.525-3311473050
SSM50M50×1.532-3812503155/56
SSM50-44M50×1.537-4413503864/55
SSM60M60×1.537-4413603366/65
SSM63M63×1.537-4413633365/68
SSM63-52M63×1.542-5213634278/68
SSM72M72×242-5215723575
Model specificationsPG thread
ModelEntry threadCable diameter range (mm)Thread length GL (mm)Thread outside diameter AG (mm)Length H (mm)Spanner size (mm)
SSPG7PG73-6.5712.51915
SSPG9PG94-8815.22018
SSPG11PG115-10818.62120
SSPG13.5PG13.56-12820.42222
SSPG16PG1610-14822.52324
SSPG21PG2113-18928.32730
SSPG29PG2918-2510373140
SSPG36PG3625-3311473750
SSPG42PG4232-3812543855/57
SSPG48PG4837-441359.33865/66
SSPG63PG6342-5215724275
Model specificationsG thread
ModelEntry threadCable diameter range (mm)Thread length GL (mm)Thread outside diameter AG (mm)Length H (mm)Spanner size (mm)
SSG1/4G1/43-6.5713.11914/16
SSG3/8G3/84-8816.62118/20
SSG1/2G1/26-12820.92222/24
SSG3/4G3/413-18926.42530
SSG1G118-2510—2940
SSG1-1/4G1-1/425-331141.93550
SSG1-1/2G1-1/232-381247.83755/56
SSG2G237-441459.63865
SSG2-1/2G2-1/242-521675.14275/80
Model specificationsNPT thread
ModelEntry threadCable diameter range (mm)Thread length GL (mm)Thread outside diameter AG (mm)Length H (mm)Spanner size (mm)
SSNPT1/4NPT1/43-6.5713.61914/16
SSNPT3/8NPT3/84-8817.02118
SSNPT1/2NPT1/26-12821.223.522
SSNPT3/4NPT3/413-18926.52630
SSNPT1NPT118-251033.23340
SSNPT1-1/4NPT1-1/422-321141.937.550
SSNPT1-1/2NPT1-1/230-381248.038.555
SSNPT2NPT237-441460.04065
SSNPT2-1/2NPT2-1/242-521672.64075/80
304 Stainless Steel Waterproof Breathable Cable Gland

Stainless-steel cable entry

304 Stainless Steel Waterproof Breathable Cable Gland

Model specificationsMetric breathable cable-entry dimensions
Entry threadCable diameter (mm)Airflow at 70 mbar (ml/min)Thread diameter AG (mm)Thread length GL (mm)Spanner size (mm)Protection rating
M10×1.53–7≥10010614IP68
M12×1.53–7≥10012614IP68
M12×1.54–8≥10012717IP68
M12×1.54–8≥200127.518IP68
M16×1.54–8≥200167.518IP68
M16×1.55–10≥300167.522IP68
M18×1.55–10≥30018822IP68
M20×1.56–12≥30020822IP68
M22×1.510–14≥50022827IP68
M25×1.510–16≥50025927IP68
M-NW Female-Thread Cable Gland for Threaded Conduit

Stainless-steel cable entry

M-NW Female-Thread Cable Gland for Threaded Conduit

Model specificationsM-NW Female-Thread Cable Gland for Threaded Conduit — thread and cable dimensions
ModelEntry threadCable diameter range (mm)Thread outside diameter (mm)Mounting hole diameter (mm)Thread Length (mm)Spanner size (mm)
M12-NWM12×1.56.5-31212-12.2714
M14-NWM14×1.58-41414-14.2717
M16-NWM16×1.58-41616-16.2818
M18-NWM18×1.510-51818-18.2820
M20-NWM20×1.512-62020-20.2822
M22-NWM22×1.514-102222-22.2824
M24-NWM24×1.514-102424-24.2924/27
M25A-NWM25×1.514-102525-25.2924/27
M25B-NWM25×1.516-82525-25.2927
M25C-NWM25×1.518-132525-25.2930/27
M27A-NWM27×1.518-132727-27.2930
M27B-NWM27×218-132727-27.2930
M28A-NWM28×1.518-132828-28.2930
M28B-NWM28×218-132828-28.2930
M30A-NWM30×1.518-133030-30.2930/32
M30B-NWM30×218-133030-30.2930/32
M32A-NWM32×1.522-153232-32.21035
M32B-NWM32×1.520-163232-32.21035
M32C-NWM32×222-153232-32.21035
M36A-NWM36×1.525-183636-36.21040
M36B-NWM36×225-183636-36.21040
M37A-NWM37×1.525-183737-37.21040
M37B-NWM37×225-183737-37.21040
M40A-NWM40×1.525-184040-40.21140/45
M40B-NWM40×225-184040-40.21140/45
M40C-NWM40×1.530-224040-40.21145
M40D-NWM40×230-224040-40.21145
M42A-NWM42×1.530-224242-42.21145
M42B-NWM42×230-224242-42.21145
M50A-NWM50×1.538-325050-50.21257/55
M50B-NWM50×238-325050-50.21257/55
M60A-NWM60×1.544-376060-60.21364
M60B-NWM60×244-376060-60.21364
M63A-NWM63×1.544-376363-63.21364/68
M63B-NWM63×244-376363-63.21364/68
M72-NWM72×252-427272-72.21578
M75-NWM75×252-427575-75.21578
M80-NWM80×262-508080-80.21886/88
M88-NWM88×270-608888-88.21898
M100-NWM100×280-70100100-100.220110
M-NLW Internal-Thread Cable Gland

Stainless-steel cable entry

M-NLW Internal-Thread Cable Gland

Model specificationsM-NLW Internal-Thread Cable Gland — thread and cable dimensions
ModelEntry threadCable diameter range (mm)Thread outside diameter (mm)Mounting hole diameter (mm)Thread Length (mm)Spanner size (mm)
M12-NLWM12×1.56.5-31212-12.2714
M14-NLWM14×1.58-41414-14.2717
M16-NLWM16×1.58-41616-16.2818
M18-NLWM18×1.510-51818-18.2820
M20-NLWM20×1.512-62020-20.2822
M22-NLWM22×1.514-102222-22.2824
M24-NLWM24×1.514-102424-24.2924/27
M25A-NLWM25×1.514-102525-25.2924/27
M25B-NLWM25×1.516-82525-25.2927
M25C-NLWM25×1.518-132525-25.2930/27
M27A-NLWM27×1.518-132727-27.2930
M27B-NLWM27×218-132727-27.2930
M28A-NLWM28×1.518-132828-28.2930
M28B-NLWM28×218-132828-28.2930
M30A-NLWM30×1.518-133030-30.2930/32
M30B-NLWM30×218-133030-30.2930/32
M32A-NLWM32×1.522-153232-32.21035
M32B-NLWM32×1.520-163232-32.21035
M32C-NLWM32×222-153232-32.21035
M36A-NLWM36×1.525-183636-36.21040
M36B-NLWM36×225-183636-36.21040
M37A-NLWM37×1.525-183737-37.21040
M37B-NLWM37×225-183737-37.21040
M40A-NLWM40×1.525-184040-40.21140/45
M40B-NLWM40×225-184040-40.21140/45
M40C-NLWM40×1.530-224040-40.21145
M40D-NLWM40×230-224040-40.21145
M42A-NLWM42×1.530-224242-42.21145
M42B-NLWM42×230-224242-42.21145
M50A-NLWM50×1.538-325050-50.21257/55
M50B-NLWM50×238-325050-50.21257/55
M60A-NLWM60×1.544-376060-60.21364
M60B-NLWM60×244-376060-60.21364
M63A-NLWM63×1.544-376363-63.21364/68
M63B-NLWM63×244-376363-63.21364/68
M72-NLWM72×252-427272-72.21578
M75-NLWM75×252-427575-75.21578
M80-NLWM80×262-508080-80.21886/88
M88-NLWM88×270-608888-88.21898
M100-NLWM100×280-70100100-100.220110
M-LBK Double-Flare Cable Gland

Stainless-steel cable entry

M-LBK Double-Flare Cable Gland

Model specificationsM-LBK Double-Flare Cable Gland — thread and cable dimensions
ModelEntry threadCable diameter range (mm)Thread outside diameter (mm)Mounting hole diameter (mm)Thread Length (mm)Spanner size (mm)
M12-LBKM12×1.56.5-31212-12.2714
M14-LBKM14×1.58-41414-14.2717
M16-LBKM16×1.58-41616-16.2818
M18-LBKM18×1.510-51818-18.2820
M20-LBKM20×1.512-62020-20.2822
M22-LBKM22×1.514-102222-22.2824
M24-LBKM24×1.514-102424-24.2924/27
M25A-LBKM25×1.514-102525-25.2924/27
M25B-LBKM25×1.516-82525-25.2927
M25C-LBKM25×1.518-132525-25.2930/27
M27A-LBKM27×1.518-132727-27.2930
M27B-LBKM27×218-132727-27.2930
M28A-LBKM28×1.518-132828-28.2930
M28B-LBKM28×218-132828-28.2930
M30A-LBKM30×1.518-133030-30.2930/32
M30B-LBKM30×218-133030-30.2930/32
M32A-LBKM32×1.522-153232-32.21035
M32B-LBKM32×1.520-163232-32.21035
M32C-LBKM32×222-153232-32.21035
M36A-LBKM36×1.525-183636-36.21040
M36B-LBKM36×225-183636-36.21040
M37A-LBKM37×1.525-183737-37.21040
M37B-LBKM37×225-183737-37.21040
M40A-LBKM40×1.525-184040-40.21140/45
M40B-LBKM40×225-184040-40.21140/45
M40C-LBKM40×1.530-224040-40.21145
M40D-LBKM40×230-224040-40.21145
M42A-LBKM42×1.530-224242-42.21145
M42B-LBKM42×230-224242-42.21145
M50A-LBKM50×1.538-325050-50.21257/55
M50B-LBKM50×238-325050-50.21257/55
M60A-LBKM60×1.544-376060-60.21364
M60B-LBKM60×244-376060-60.21364
M63A-LBKM63×1.544-376363-63.21364/68
M63B-LBKM63×244-376363-63.21364/68
M72-LBKM72×252-427272-72.21578
M75-LBKM75×252-427575-75.21578
M80-LBKM80×262-508080-80.21886/88
M88-LBKM88×270-608888-88.21898
M100-LBKM100×280-70100100-100.220110
MG-Series EMC Cable Gland

Stainless-steel cable entry

MG-Series EMC Cable Gland

Model specificationsMetric thread
ModelEntry threadCable diameter range (mm)Thread outside diameter (mm)Mounting hole diameter (mm)Thread length GL (mm)Spanner size (mm)Joint length H (mm)
E.M12A-EMCM 12X1.53-5.31212-12.3817/17—
E.M12B-EMCM 12X1.54.5-7.81212-12.3817/17—
E.M16A-EMCM16X1.54-71616-16.3922/22—
E.M16B-EMCM16X1.56-101616-16.3922/22—
E.M20A-EMCM20X1.55-8.82020-20.39.524/24—
E.M20B-EMCM20X1.57-122020-20.39.524/24—
E.M20C-EMCM20X1.59-142020-20.39.526/26—
E.M25A-EMCM25X1.512-162525-25.492727
E.M25B-EMCM25X1.514-182525-25.41232/32—
E.M32A-EMCM32X1.516-223232-32.412.541/41—
E.M32B-EMCM32X1.518-253232-32.41040/3531
E.M40A-EMCM40X1.521-254040-40.41550/50—
E.M40B-EMCM40X1.524-304040-40.41550/50—
E.M50A-EMCM50X1.526-325050-50.41560/60—
E.M50B-EMCM50X1.531-415050-50.41560/60—
E.M63A-EMCM63X1.540-466363-63.41573/73—
E.M63B-EMCM63X1.544-516363-63.41573/73—
E.M75A-EMCM75X1.550-567575-75.61585/85—
E.M75B-EMCM75X1.556-667575-75.61585/85—
E.M90A-EMCM90X1.558-689090-9120102/102—
E.M90B-EMCM90X1.566-779090-9120102/102—
E.M100A-EMCM100X1.558-68100100-10125116/116—
E.M100B-EMCM100X1.566-77100100-10125116/116—
Model specificationsPG thread
ModelEntry threadCable diameter range (mm)Thread outside diameter (mm)Mounting hole diameter (mm)Thread length GL (mm)Spanner size (mm)
E.PG7A-EMCPG7-EMC3-5.312.512.5-12.8817/17
E.PG7B-EMCPG7-EMC4.5-7.812.512.5-12.5817/17
E.PG9A-EMCPG9-EMC3-5.815.215.2-15.5818/18
E.PG9B-EMCPG9-EMC4.5-7.815.215.2-15.5818/18
E.PG11A-EMCPG11-EMC4-718.618.6-18.9922/22
E.PG11B-EMCPG11-EMC6-1018.618.6-18.9922/22
E.PG13.5A-EMCPG13.5-EMC5-8.820.420.4-20.79.524/24
E.PG13.5B-EMCPG13.5-EMC7-1220.420.4-20.79.524/24
E.PG16A-EMCPG16-EMC7-1122.522.5-22.89.526/26
E.PG16B-EMCPG16-EMC9-1422.522.5-22.89.526/26
E.PG21A-EMCPG21-EMC12-1628.328.3-28.71232/32
E.PG21B-EMCPG21-EMC14-1828.328.3-28.71232/32
E.PG29A-EMCPG29-EMC16-223737-37.412.541/41
E.PG29B-EMCPG29-EMC18-253737-37.412.541/41
E.PG36A-EMCPG36-EMC21-254747-47.41550/50
E.PG36B-EMCPG36-EMC24-304747-47.41550/50
Model specificationsG/NPT threads
ModelEntry threadCable diameter range (mm)Thread outside diameter (mm)Mounting hole diameter (mm)Thread length GL (mm)Spanner size (mm)
E.G3/8A-EMCG(PF)3/8 “4-716.66216.7-16.9922/22
E.G3/8B-EMCG(PF)3/8 “6-1016.66216.7-16.9922/22
E.G3/4A-EMCG(PF)3/4 “12-1626.44126.5-26.81232/32
E.G3/4B-EMCG(PF)3/4 “14-1826.44126.5-26.81232/32
E.G1A-EMCG(PF)1″16-2233.24933.3-33.612.541/41
E.G1B-EMCG(PF)1″18-2533.24933.3-33.612.541/41
E.G11/4A-EMCG(PF)1-1/4″21-2541.9142-42.31550/50
E.G11/4B-EMCG(PF)1-1/4″24-3041.9142-42.31550/50
E.G11/2A-EMCG(PF)1-1/2 “26-3247.80348-48.41560/60
E.G11/2B-EMCG(PF)1-1/2 “31-4147.80348-48.41560/60
E.G2A-EMCG(PF)2 “40-4659.61460-60.41573/73
E.G2B-EMCG(PF)2 “44-5159.61460-60.41573/73
E.G21/2-EMCG(PF)2-1/2 “50-5675.18475.2-75.61885/88
E.G21/2-EMCG(PF)2-1/2 “66-5675.18475.2-75.61885/88
E.NPT3/8A-EMCNPT3/8 “4-717.0551322
E.NPT3/8B-EMCNPT3/8 “6-1017.0551322
E.NPT1/2A-EMCNPT1/2 “7-1121.2231326
E.NPT1/2B-EMCNPT1/2 “9-1421.2231326
E.NPT3/4A-EMCNPT3/4 “12-1626.5681432
E.NPT3/4B-EMCNPT3/4 “14-1826.5681432
E.NPT1A-EMCNPT1 “16-2233.2271541
E.NPT1B-EMCNPT1 “18-2533.2271541
E.NPT11/4A-EMCNPT 1-1/4 “21-2541.9841550
E.NPT11/4B-EMCNPT 1-1/4 “240-3041.9841550
Spring-Contact EMC Cable Gland

Stainless-steel cable entry

Spring-Contact EMC Cable Gland

Model specificationsMetric thread
ModelHeight (mm)Thread length (mm)Cable diameter range (mm)Spanner size (mm)
B.M12-EMC2063-716
B.M16-EMC2474-1020
B.M20-EMC2796-1324
B.M25-EMC2989-1730
B.M32-EMC33911-2136
B.M40-EMC41919-2845
B.M5O-EMC45926-3555
B.M63-EMC481434-4568
Model specificationsPG thread
ModelHeight (mm)Thread length (mm)Cable diameter range (mm)Spanner size (mm)
B.PG7-EMC1953-6.514
B.PG9-EMC2264-817
B.PG11-EMC2565-1020
B.PG13.5-EMC266.56-1222
B.PG16-EMC276.510-1424
B.PG21-EMC31713-1830
B.PG29-EMC38818-2540
B.PG36-EMC451522-3250
B.PG42-EMC451530-3857
B.PG48-EMC471534-4464
D-Series EMC Cable Gland

Stainless-steel cable entry

D-Series EMC Cable Gland

Model specificationsPG thread
ModelThreadCable diameter range (mm)Thread outside diameter (mm)Plate diameter (mm)Thread length GL (mm)Joint length H (mm)Spanner size (mm)
D.PG7-EMCPG76.5-312.512.5-12.771914
D.PG9-EMCPG98-415.215.2-15.482017
D.PG11-EMCPG1110-518.618.6-18.882120/21
D.PG13.5-EMCPG13.512-620.420.4-20.682222
D.PG16-EMCPG1614-1022.522.5-22.792324
D.PG19-EMCPG1914-102525-25.292524/27
D.PG21-EMCPG2118-1328.328.3-28.592730
D.PG25-EMCPG2522-153232-32.2102935
D.PG29-EMCPG2925-183737-37.2103140
D.PG36-EMCPG3633-254747-47.2113750
D.PG42-EMCPG4238-325454-54.2133857
D.PG48-EMCPG4844-3759.359.3-59.5143864
D.PG63-EMCPG6352-427272-72.2154278
Model specificationsMetric thread
ModelThreadCable diameter range (mm)Thread outside diameter (mm)Plate diameter (mm)Thread length GL (mm)Joint length H (mm)Spanner size (mm)
D.M12-EMCM12*1.56.5-31212-12.271914
D.M14-EMCM14*1.58-41414-14.271917
D.M16-EMCM16*1.58-41616-16.282018
D.M18-EMCM18*1.510-51818-18.282120
D.M20-EMCM20*1.512-62020-20.282222
D.M22-EMCM22*1.514-102222-22.282324
D.M24-EMCM24*1.514-102424-24.292524/27
D.M25A-EMCM25*1.514-102525-25.292524/27
D.M25B-EMCM25*1.518-132525-25.292730/27
D.M27A-EMCM27*1.518-132727-27.292730
D.M27B-EMCM27*218-132727-27.292730
D.M28A-EMCM28*1.518-132828-28.292730
D.M28B-EMCM28*218-132828-28.292730
D.M30A-EMCM30*1.518-133030-30.292930/32
D.M30B-EMCM30*218-133030-30.292930/32
D.M32A-EMCM32*1.522-153232-32.2102935
D.M32B-EMCM32*222-153232-32.2102935
D.M33A-EMCM33*1.522-153333-33.2102935
D.M33B-EMCM33*222-153333-33.2102935
D.M36A-EMCM36*1.525-183636-36.2103140
D.M36B-EMCM36*225-183636-36.2103140
D.M37A-EMCM37*1.525-183737-37.2103140
D.M37B-EMCM37*225-183737-37.2103140
D.M40A-EMCM40*1.525-184040-40.2113140/45
D.M40B-EMCM40*225-184040-40.2113140/45
D.M40C-EMCM40*1.530-224040-40.2113545
D.M40D-EMCM40*230-224040-40.2113545
D.M42A-EMCM42*1.530-224242-42.2113545
D.M42B-EMCM42*230-224242-42.2113545
D.M47A-EMCM47*1.533-254747-47.2113750
D.M47B-EMCM47*233-254747-47.2113750
D.M48A-EMCM48*1.533-254848-48.2113750/52
D.M48B-EMCM48*233-254848-48.2113750/52
D.M50A-EMCM50*1.538-325050-50.2123750/55
D.M50B-EMCM50*238-325050-50.2123750/55
D.M54A-EMCM54*1.538-325454-54.2123857
D.M54B-EMCM54*238-325454-54.2123857
D.M56A-EMCM56*1.538-325656-56.2123857/59
D.M56B-EMCM56*238-325656-56.2123857/59
D.M60A-EMCM60*1.544-376060-60.2133864
D.M60B-EMCM60*244-376060-60.2133864
D.M63A-EMCM63*1.544-376363-63.2133864/68
D.M63B-EMCM63*244-376363-63.2133864/68
D.M64A-EMCM64*1.544-376464-64.2133864/68
D.M64B-EMCM64*244-376464-64.2133864/68
D.M72-EMCM72*252-427272-72.2154265/68
D.M75-EMCM75*252-427575-75.2154278
D.M80-EMCM80*262-508080-80.2154586/88
D.M88-EMCM88*270-608888-88.2154598
D.M100-EMCM100*280-70100100-100.21545110
Model specificationsG/NPT threads
ModelThreadCable diameter range (mm)Thread outside diameter (mm)Threads per inchThread length GL (mm)Joint length H (mm)Spanner size (mm)
D.G1/4-EMCG1/46.5-313.11971914
D.G3/8-EMCG3/88-416.61981918
D.G1/2-EMCG1/212-620.91482222
D.G3/4-EMCG3/418-1326.41492530
D.G1-EMCG125-1833.211112940
D.G1-1/4-EMCG1-1/433-2541.911133550
D.G1-1/2-EMCG1-1/238-3247.811143757
D.G2-EMCG244-3759.611143864
D.G2-1/2-EMCG2-1/252-4275.111153877
D.G3-EMCG370-6587.811154894
D.NPT1/4-EMCNPT1/46.5-313.61871914
D.NPT3/8-EMCNPT3/88-4171881918
D.NPT1/2-EMCNPT1/212-621.21482222
D.NPT3/4-EMCNPT3/418-1326.51492530
D.NPT1-EMCNPT125-1833.211.5112940
D.NPT1-1/4-EMCNPT1-1/433-2541.911.5133550
D.NPT1-1/2-EMCNPT1-1/238-324811.5143757
D.NPT2-EMCNPT244-376011.5143864
D.NPT2-1/2-EMCNPT2-1/252-4272.68153878
D.NPT3-EMCNPT370-6588.68154598
F-Series EMC Cable Gland for Metric Entries

Stainless-steel cable entry

F-Series EMC Cable Gland for Metric Entries

Model specificationsF-Series EMC Cable Gland for Metric Entries — thread and cable dimensions
ModelThread AGCable diameter range (mm)Spanner size (mm)Diagonal Size (mm)
F.M20A-EMCM20*1.56-122224.5
F.M20B-EMCM20*1.55-92224.6
F.M20C-EMCM20*1.510-142426.6
F.M20D-EMCM20*1.57-122426.6
F.M25A-EMCM25*1.513-183034
F.M25B-EMCM25*1.59-163034
F.M32A-EMCM32*1.518-254044.5
F.M32B-EMCM32*1.513-204044.5
F.M40A-EMCM40*1.522-325055
F.M40B-EMCM40*1.520-265055
F.M50A-EMCM50*1.532-385762
F.M50B-EMCM50*1.525-315762
F.M63A-EMCM63*1.537-446572
F.M63B-EMCM63*1.529-356572
Ex-VI Clamping Gland for Unarmoured Cable

Stainless-steel cable entry

Ex-VI Clamping Gland for Unarmoured Cable

Model specificationsMetric thread
Metric ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
M16 × 1.5Ex-VIM168-14151624
M20 × 1.5Ex-VIM208-14152024
M25 × 1.5Ex-VIM258-17152530
M32 × 1.5Ex-VIM3212-24173238
M40 × 1.5Ex-VIM4018-30174045
M50 × 1.5Ex-VIM5024-36205055
M63 × 1.5Ex-VIM6330-46206368
M75 × 2.0Ex-VIM7536-60227580
M88 × 2.0Ex-VIM8858-72228896
M110 × 2.0Ex-VIM11066-9022110125
Model specificationsNPT thread
NPT ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
NPT 3/8Ex-VINPT3/88-141517.0524
NPT 1/2Ex-VINPT1/28-141521.2224
NPT 3/4Ex-VINPT3/48-171526.5630
NPT 1Ex-VINPT112-241733.2838
NPT 1-1/4Ex-VINPT1-1/418-301741.9845
NPT 1-1/2Ex-VINPT1-1/224-362048.0555
NPT 2Ex-VINPT230-462060.0968
NPT 2-1/2Ex-VINPT2-1/236-602272.6980
NPT 3Ex-VINPT358-722288.6096
NPT 4Ex-VINPT466-9022113.97125
Model specificationsG thread
G ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
G 3/8Ex-VIG3/88-141516.6624
G 1/2Ex-VIG1/28-141520.9524
G 3/4Ex-VIG3/48-171526.4430
G 1Ex-VIG112-241733.2538
G 1-1/4Ex-VIG1-1/418-301741.9145
G 1-1/2Ex-VIG1-1/224-362047.8055
G 2Ex-VIG230-462059.6168
G 2-1/2Ex-VIG2-1/236-602275.1880
G 3Ex-VIG358-722287.8896
G 4Ex-VIG466-9022113.03125
Ex-VIG Clamping Gland for Unarmoured Cable

Stainless-steel cable entry

Ex-VIG Clamping Gland for Unarmoured Cable

Model specificationsMetric thread
Metric ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
M16 × 1.5Ex-VIGM168-14151624
M20 × 1.5Ex-VIGM205-14152024
M25 × 1.5Ex-VIGM255-17152530
M32 × 1.5Ex-VIGM328-24173238
M40 × 1.5Ex-VIGM4010-30174045
M50 × 1.5Ex-VIGM5012-36205055
M63 × 1.5Ex-VIGM6318-46206368
M75 × 2.0Ex-VIGM7520-60227580
M88 × 2.0Ex-VIGM8822-72228896
M110 × 2.0Ex-VIGM11030-9022110125
Model specificationsNPT thread
NPT ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
NPT 3/8Ex-VIGNPT3/88-141517.0524
NPT 1/2Ex-VIGNPT1/25-141521.2224
NPT 3/4Ex-VIGNPT3/45-171526.5630
NPT 1Ex-VIGNPT18-241733.2838
NPT 1-1/4Ex-VIGNPT1-1/410-301741.9845
NPT 1 1/2Ex-VIGNPT1-1/212-362048.0555
NPT 2Ex-VIGNPT218-462060.0968
NPT 2-1/2Ex-VIGNPT2-1/220-602272.6980
NPT 3Ex-VIGNPT322-722288.6096
NPT 4Ex-VIGNPT430-9022113.97125
Model specificationsG thread
G ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
G 3/8Ex-VIGG3/88-141516.6624
G 1/2Ex-VIGG1/25-141520.9524
G 3/4Ex-VIGG3/45-171526.4430
G 1Ex-VIGG18-241733.2538
G 1-1/4Ex-VIGG1-1/410-301741.9145
G 1-1/2Ex-VIGG1-1/212-362047.8055
G 2Ex-VIGG218-462059.6168
G 2-1/2Ex-VIGG2-1/220-602275.1880
G 3Ex-VIGG322-722287.8896
G 4Ex-VIGG430-9022113.03125
Ex-VIIIG Single-Seal Armoured Cable Gland

Stainless-steel cable entry

Ex-VIIIG Single-Seal Armoured Cable Gland

Model specificationsMetric thread
Metric ThreadModelLocking Range (mm)Max. Outlet (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
M16 × 1.5Ex-VIIIGM165-1612151624
M20 × 1.5Ex-VIIIGM205-1612152024
M20 × 1.5DEx-VIIIGM20D9-2016152030
M25 × 1.5Ex-VIIIGM259-2016152530
M25 × 1.5DEx-VIIIGM25D14-2620152538
M32 × 1.5Ex-VIIIGM3214-2620173238
M32 × 1.5DEx-VIIIGM32D18-3328173245
M40 × 1.5Ex-VIIIGM40-3318-3328174045
M40 × 1.5DEx-VIIIGM40D20-4035174055
M50 × 1.5Ex-VIIIGM5020-4035205055
M50 × 1.5DEx-VIIIGM50D26-5045205068
M63 × 1.5Ex-VIIIGM6326-5045206368
M63 × 1.5DEx-VIIIGM63D30-6455206382
M75 × 2Ex-VIIIGM7530-6455227582
M88 × 2Ex-VIIIGM8836-8070228898
M100 × 2Ex-VIIIGM10041-908022100110
M115 × 2Ex-VIIIGM11547-1039022115125
M130 × 2Ex-VIIIGM13063-11910022130140
Model specificationsNPT thread
NPT ThreadModelLocking Range (mm)Max. Outlet (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
NPT 3/8Ex-VIIIGNPT3/85-16121517.0524
NPT 1/2Ex-VIIIGNPT1/25-16121521.2224
NPT 1/2DEx-VIIIGNPT1/2D9-20161521.2230
NPT 3/4Ex-VIIIGNPT3/49-20161526.5630
NPT 3/4DEx-VIIIGNPT3/4D14-26201526.5638
NPT 1Ex-VIIIGNPT114-26201733.2838
NPT 1DEx-VIIIGNPT1D18-33281733.2845
NPT 1-1/4Ex-VIIIGNPT1-1/418-33281741.9845
NPT 1-1/4DEx-VIIIGNPT1-1/4D20-40351741.9855
NPT 1-1/2Ex-VIIIGNPT1-1/220-40352048.0555
NPT 1-1/2DEx-VIIIGNPT1-1/2D26-50452048.0568
NPT 2Ex-VIIIGNPT226-50452060.0968
NPT 2DEx-VIIIGNPT2D30-64552060.0982
NPT 2-1/2Ex-VIIIGNPT2-1/230-64552272.6982
NPT 3Ex-VIIIGNPT336-80702288.6098
NPT 4Ex-VIIIGNPT447-1039022113.97125
Model specificationsG thread
G ThreadModelLocking Range (mm)Max. Outlet (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
G 3/8Ex-VIIIGG3/85-16121516.6624
G 1/2Ex-VIIIGG1/25-16121520.9524
G 1/2DEx-VIIIGG1/2D9-20161520.9530
G 3/4Ex-VIIIGG3/49-20161526.4430
G 3/4DEx-VIIIGG3/4D14-26201526.4438
G 1Ex-VIIIGG114-26201733.2538
G 1DEx-VIIIGG1D18-33281733.2545
G 1-1/4Ex-VIIIGG1-1/418-33281741.9145
G 1-1/4DEx-VIIIGG1-1/4D20-40351741.9155
G 1-1/2Ex-VIIIGG1-1/220-40352047.8055
G 1-1/2DEx-VIIIGG1-1/2D26-50452047.8068
G 2Ex-VIIIGG226-50452059.6168
G 2DEx-VIIIGG2D30-64552059.6182
G 2-1/2Ex-VIIIGG2-1/230-64552275.1882
G 3Ex-VIIIGG336-80702287.8898
G 4Ex-VIIIGG447-1039022113.03125
Ex-VIIG Double-Seal Armoured Cable Gland

Stainless-steel cable entry

Ex-VIIG Double-Seal Armoured Cable Gland

Model specificationsMetric thread
Metric ThreadModelLocking Range (mm)Max. Outlet (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
M16 × 1.5Ex-VIIGM165-1612151624
M20 × 1.5Ex-VIIGM205-1612152024
M20 × 1.5DEx-VIIGM20D9-2016152030
M25 × 1.5Ex-VIIGM259-2016152530
M25 × 1.5DEx-VIIGM25D14-2620152538
M32 × 1.5Ex-VIIGM3214-2620173238
M32 × 1.5DEx-VIIGM32D18-3328173245
M40 × 1.5Ex-VIIGM40-3318-3328174045
M40 × 1.5DEx-VIIGM40D20-4035174055
M50 × 1.5Ex-VIIGM5020-4035205055
M50 × 1.5DEx-VIIGM50D26-5045205068
M63 × 1.5Ex-VIIGM6326-5045206368
M63 × 1.5DEx-VIIGM63D30-6455206382
M75 × 2Ex-VIIGM7530-6455227582
M88 × 2Ex-VIIGM8836-8070228898
M100 × 2Ex-VIIGM10041-908022100110
M115 × 2Ex-VIIGM11547-1039022115125
M130 × 2Ex-VIIGM13063-11910022130140
Model specificationsNPT thread
NPT ThreadModelLocking Range (mm)Max. Outlet (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
NPT 3/8Ex-VIIGNPT3/85-16121517.0524
NPT 1/2Ex-VIIGNPT1/25-16121521.2224
NPT 1/2DEx-VIIGNPT1/2D9-20161521.2230
NPT 3/4Ex-VIIGNPT3/49-20161526.5630
NPT 3/4DEx-VIIGNPT3/4D14-26201526.5638
NPT 1Ex-VIIGNPT114-26201733.2838
NPT 1DEx-VIIGNPT1D18-33281733.2845
NPT 1-1/4Ex-VIIGNPT1-1/418-33281741.9845
NPT 1-1/4DEx-VIIGNPT1-1/4D20-40351741.9855
NPT 1-1/2Ex-VIIGNPT1-1/220-40352048.0555
NPT 1-1/2DEx-VIIGNPT1-1/2D26-50452048.0568
NPT 2Ex-VIIGNPT226-50452060.0968
NPT 2DEx-VIIGNPT2D30-64552060.0982
NPT 2-1/2Ex-VIIGNPT2-1/230-64552272.6982
NPT 3Ex-VIIGNPT336-80702288.6098
NPT 4Ex-VIIGNPT447-1039022113.97125
Model specificationsG thread
G ThreadModelLocking Range (mm)Max. Outlet (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
G 3/8Ex-VIIGG3/85-16121516.6624
G 1/2Ex-VIIGG1/25-16121520.9524
G 1/2DEx-VIIGG1/2D9-20161520.9530
G 3/4Ex-VIIGG3/49-20161526.4430
G 3/4DEx-VIIGG3/4D14-26201526.4438
G 1Ex-VIIGG114-26201733.2538
G 1DEx-VIIGG1D18-33281733.2545
G 1-1/4Ex-VIIGG1-1/418-33281741.9145
G 1-1/4DEx-VIIGG1-1/4D20-40351741.9155
G 1-1/2Ex-VIIGG1-1/220-40352047.8055
G 1-1/2DEx-VIIGG1-1/2D26-50452047.8068
G 2Ex-VIIGG226-50452059.6168
G 2DEx-VIIGG2D30-64552059.6182
G 2-1/2Ex-VIIGG2-1/230-64552275.1882
G 3Ex-VIIGG336-80702287.8898
G 4Ex-VIIGG447-1039022113.03125
Ex-BG Clamping Gland for Unarmoured Cable

Stainless-steel cable entry

Ex-BG Clamping Gland for Unarmoured Cable

Model specificationsMetric thread
Metric ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
M12 × 1.5Ex-BGM12-84-8121218/18
M14 × 1.5Ex-BGM14-84-8121418/18
M16 × 1.5Ex-BGM16-84-8121618/18
M16 × 1.5Ex-BGM16-105-10121622/22
M18 × 1.5Ex-BGM18-105-10121822/22
M20 × 1.5Ex-BGM20-105-10122022/24
M20 × 1.5Ex-BGM20-128-12122024/24
M20 × 1.5Ex-BGM20-1410-14122026/26
M22 × 1.5Ex-BGM22-1410-14122226/26
M24 × 1.5Ex-BGM24-1410-14122426/26
M25 × 1.5Ex-BGM25-128-12152524/30
M25 × 1.5Ex-BGM25-1410-14152526/30
M25 × 1.5Ex-BGM25-1813-18152532/32
M27 × 1.5Ex-BGM27-1813-18152732/32
M30 × 1.5Ex-BGM30-1813-18153032/32
M32 × 1.5Ex-BGM32-2518-25173240/40
M36 × 1.5Ex-BGM36-2518-25173640/40
M40 × 1.5Ex-BGM40-3225-32174050/50
M48 × 1.5Ex-BGM48-3225-32174850/50
M50 × 1.5Ex-BGM50-3932-39175060/60
M60 × 1.5Ex-BGM60-4436-44176065/65
M63 × 1.5Ex-BGM63-4436-44176365/68
M63 × 1.5Ex-BGM63-5445-54176375/75
M64 × 2.0Ex-BGM64-5445-54176475/75
M72 × 1.5Ex-BGM72-5445-54207280/80
M75 × 2.0Ex-BGM75-6655-66207585/90
M78 × 2.0Ex-BGM78-6655-66207890/90
M80 × 2.0Ex-BGM80-6655-66208090/90
M88 × 2.0Ex-BGM88-7767-7720—100/100
M90 × 2.0Ex-BGM90-7767-772090100/100
M100 × 2.0Ex-BGM100-8778-8720100110/110
M110 × 2.0Ex-BGM110-9988-9920110120/120
M120 × 2.0Ex-BGM120-10899-10820120130/130
Model specificationsNPT thread
NPT ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
NPT 1/4Ex-BGNPT1/4-84-81213.6118/18
NPT 3/8Ex-BGNPT3/8-106-101217.0522/22
NPT 1/2-SEx-BGNPT1/2S-128-121221.2224/24
NPT 1/2-DEx-BGNPT1/2D-1410-141221.2226/26
NPT 3/4Ex-BGNPT3/4-106-101526.5622/32
NPT 3/4Ex-BGNPT3/4-1410-141526.5626/32
NPT 3/4Ex-BGNPT3/4-1813-181526.5632/32
NPT 1Ex-BGNPT1-2518-251733.2840/40
NPT 1-1/4Ex-BGNPT1-1/4-3225-321741.9850/50
NPT 1-1/2Ex-BGNPT1-1/2-3225-321748.0550/52
NPT 1-1/2Ex-BGNPT1-1/2-3932-391748.0552/52
NPT 2-SEx-BGNPT2S-4437-441760.0965/65
NPT 2-1/2Ex-BGNPT2-1/2-5444-542072.6975/85
NPT 2-1/2Ex-BGNPT2-1/2-6654-662072.6985/85
NPT 3-SEx-BGNPT3S-7766-772088.60100/100
NPT 4-SEx-BGNPT4S-9988-9920113.97122/122
Model specificationsG thread
G ThreadModelLocking Range (mm)Thread Length GL (mm)Thread outside diameter AG (mm)Spanner size (mm)
G 1/4Ex-BGG1/4-84-81213.1518/18
G 3/8Ex-BGG3/8-106-101216.6622/22
G 1/2-SEx-BGG1/2S-128-121220.9524/24
G 1/2-DEx-BGG1/2D-1410-141220.9526/26
G 3/4Ex-BGG3/4-106-101526.4422/32
G 3/4Ex-BGG3/4-1410-141526.4426/32
G 3/4Ex-BGG3/4-1813-181526.4432/32
G 1Ex-BGG1-2518-251733.2540/40
G 1-1/4Ex-BGG1-1/4-3225-321741.9150/50
G 1-1/2Ex-BGG1-1/2-3225-321747.8050/52
G 1-1/2Ex-BGG1-1/2-3932-391747.8052/52
G 2Ex-BGG2-4437-441759.6165/65
G 2-1/2Ex-BGG2-1/2-5444-542075.1875/85
G 2-1/2Ex-BGG2-1/2-6654-662075.1885/85
G 3Ex-BGG3-7766-772087.88100/100
G 4Ex-BGG4-9988-9920113.03122/122
BDM-BDT / Ex-BDT Threaded Stopping Plug

Stainless-steel cable entry

BDM-BDT / Ex-BDT Threaded Stopping Plug

Model specificationsMetric thread
Metric ThreadModelThread Length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Opposite side (mm)
M16×1.5Ex-BDTM1615161920
M20×1.5Ex-BDTM2015201924
M25×1.5Ex-BDTM2515252030
M32×1.5Ex-BDTM3217322236
M40×1.5Ex-BDTM4017402345
M50×1.5Ex-BDTM5020502755
M60×1.5Ex-BDTM6020602764
M63×1.5Ex-BDTM6320632768
M75×2.0Ex-BDTM7522753080
M88×2.0Ex-BDTM8822883196
M100×2.0Ex-BDTM1002210032110
M115×2.0Ex-BDTM1152211533125
Model specificationsNPT thread
American ThreadModelThread Length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Opposite side (mm)
NPT1/2Ex-BDTNPT1/21521.221924
NPT3/4Ex-BDTNPT3/41526.562030
NPT1Ex-BDTNPT11733.282236
NPT1-1/4Ex-BDTNPT1-1/41741.982345
NPT1-1/2Ex-BDTNPT1-1/22048.052755
NPT2Ex-BDTNPT22060.092764
NPT2-1/2Ex-BDTNPT2-1/22272.693080
NPT3Ex-BDTNPT32288.603196
NPT4Ex-BDTNPT422113.9733125
Model specificationsG thread
Inch ThreadModelThread Length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Opposite side (mm)
G1/2Ex-BDTG1/21520.951924
G3/4Ex-BDTG3/41526.442030
G1Ex-BDTG11733.252236
G1-1/4Ex-BDTG1-1/41741.912345
G1-1/2Ex-BDTG1-1/22047.802755
G2Ex-BDTG22059.612764
G2-1/2Ex-BDTG2-1/22275.183080
G3Ex-BDTG32287.883196
G4Ex-BDTG422113.0333125
BGJ-A Female-to-Female Pipe Coupler

Stainless-steel cable entry

BGJ-A Female-to-Female Pipe Coupler

Model specificationsMetric thread
Metric ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
M16×1.5BGJAM1615163422
M20×1.5BGJAM2015203427
M25×1.5BGJAM2515253432
M32×1.5BGJAM3217323938
M40×1.5BGJAM4017403947
M50×1.5BGJAM5020504657
M63×1.5BGJAM6320634668
M75×2.0BGJAM7520754784
M90×2.0BGJAM9020904798
M115×2.0BGJAM1152011548125
Model specificationsNPT thread
American ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
NPT3/8BGJANPT3/81517.053422
NPT1/2BGJANPT1/21521.223427
NPT3/4BGJANPT3/41526.563432
NPT1BGJANPT11733.283938
NPT1-1/4BGJANPT1-1/41741.983947
NPT1-1/2BGJANPT1-1/22048.054657
NPT2BGJANPT22060.094668
NPT2-1/2BGJANPT2-1/22072.694784
NPT3BGJANPT32088.604798
NPT4BGJANPT420113.9748125
Model specificationsG thread
Inch ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
G3/8BGJAG3/81516.663422
G1/2BGJAG1/21520.953427
G3/4BGJAG3/41526.443432
G1BGJAG11733.253938
G1-1/4BGJAG1-1/41741.913947
G1-1/2BGJAG1-1/22047.804657
G2BGJAG22059.614668
G2-1/2BGJAG2-1/22075.184784
G3BGJAG32087.884798
G4BGJAG420113.0348125
BGJ-B Thread Adapter — Reducer and Enlarger

Stainless-steel cable entry

BGJ-B Thread Adapter — Reducer and Enlarger

Model specificationsMetric thread
Metric ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
M16×1.5BGJBM1615163422
M20×1.5BGJBM2015203427
M25×1.5BGJBM2515253432
M32×1.5BGJBM3217323938
M40×1.5BGJBM4017403947
M50×1.5BGJBM5020504657
M63×1.5BGJBM6320634668
M75×2.0BGJBM7520754784
M90×2.0BGJBM9020904798
M115×2.0BGJBM1152011548125
Model specificationsNPT thread
American ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
NPT3/8BGJBNPT3/81517.053422
NPT1/2BGJBNPT1/21521.223427
NPT3/4BGJBNPT3/41526.563432
NPT1BGJBNPT11733.283938
NPT1-1/4BGJBNPT1-1/41741.983947
NPT1-1/2BGJBNPT1-1/22048.054657
NPT2BGJBNPT22060.094668
NPT2-1/2BGJBNPT2-1/22072.694784
NPT3BGJBNPT32088.604798
NPT4BGJBNPT420113.9748125
Model specificationsG thread
Inch ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
G3/8BGJBG3/81516.663422
G1/2BGJBG1/21520.953427
G3/4BGJBG3/41526.443432
G1BGJBG11733.253938
G1-1/4BGJBG1-1/41741.913947
G1-1/2BGJBG1-1/22047.804657
G2BGJBG22059.614668
G2-1/2BGJBG2-1/22075.184784
G3BGJBG32087.884798
G4BGJBG420113.0348125
BGJ-C Male-to-Male Reducing Nipple

Stainless-steel cable entry

BGJ-C Male-to-Male Reducing Nipple

Model specificationsMetric thread
Metric ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
M16×1.5BGJCM1615163420
M20×1.5BGJCM2015203424
M25×1.5BGJCM2515253430
M32×1.5BGJCM3217323938
M40×1.5BGJCM4017403945
M50×1.5BGJCM5020504655
M63×1.5BGJCM6320634668
M75×2.0BGJCM7520754780
M90×2.0BGJCM9020904798
M115×2.0BGJCM1152011548120
Model specificationsNPT thread
American ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
NPT3/8BGJCNPT3/81517.053420
NPT1/2BGJCNPT1/21521.223424
NPT3/4BGJCNPT3/41526.563430
NPT1BGJCNPT11733.283938
NPT1-1/4BGJCNPT1-1/41741.983945
NPT1-1/2BGJCNPT1-1/22048.054655
NPT2BGJCNPT22060.094668
NPT2-1/2BGJCNPT2-1/22072.694780
NPT3BGJCNPT32088.604798
NPT4BGJCNPT420113.9748120
Model specificationsG thread
Inch ThreadModelThread length GL (mm)Thread outside diameter AG (mm)Overall Length OL(mm)Spanner size (mm)
G3/8BGJCG3/81516.663420
G1/2BGJCG1/21520.953424
G3/4BGJCG3/41526.443430
G1BGJCG11733.253938
G1-1/4BGJCG1-1/41741.913945
G1-1/2BGJCG1-1/22047.804655
G2BGJCG22059.614668
G2-1/2BGJCG2-1/22075.184780
G3BGJCG32087.884798
G4BGJCG420113.0348120
BGJ-D Male-to-Female Reducing Bushing

Stainless-steel cable entry

BGJ-D Male-to-Female Reducing Bushing

Model specificationsMetric thread
Thread sizesModelMale threadInternal threadThread outside diameter AG (mm)Overall length (mm)Spanner size (mm)
M20-M16BGJDM16M20x1.5M16x1.520-162224
M25-M20BGJDM20M25x1.5M20x1.525-202524
M32-M25BGJDM25M32x1.5M25x1.532-252830
M40-M32BGJDM32M40x1.5M32x1.540-323038
M50-M40BGJDM40M50x1.5M40x1.550-403045
M63-M50BGJDM50M63x1.5M50x1.563-503255
M75-M63BGJDM63M75x1.5M63x1.575-633568
M90-M75BGJDM75M90x2M75x1.590-753680
M115-M90BGJDM90M115x2M90x2115-903698
Model specificationsNPT thread
Thread sizesModelMale threadInternal threadThread outside diameter AG (mm)Overall length (mm)Spanner size (mm)
NPT1/2-NPT3/8BGJDNPT3/8NPT1/2NPT3/821.22-17.052224
NPT3/4-NPT1/2BGJDNPT1/2NPT3/4NPT1/226.56-21.222524
NPT1-NPT3/4BGJDNPT3/4NPT1NPT3/433.28-26.562830
NPT1-1/4-NPT1BGJDNPT1NPT1-1/4NPT141.98-33.283038
NPT1-1/2-NPT1-1/4BGJDNPT1-1/4NPT1-1/2NPT1-1/448.05-41.983045
NPT2-NPT1-1/2BGJDNPT1-1/2NPT2NPT1-1/260.09-48.053255
NPT2-1/2-NPT2BGJDNPT2NPT2-1/2NPT272.69-60.093568
NPT3-NPT2-1/2BGJDNPT2-1/2NPT3NPT2-1/288.60-72.693680
NPT4-NPT3BGJDNPT3NPT4NPT3113.97-88.603698
Model specificationsG thread
Thread sizesModelMale threadInternal threadThread outside diameter AG (mm)Overall length (mm)Spanner size (mm)
G1/2-G3/8BGJDG3/8G1/2G3/820.95-16.662224
G3/4-G1/2BGJDG1/2G3/4G1/226.44-20.952524
G1-G3/4BGJDG3/4G1G3/433.25-26.442830
G1-1/4-G1BGJDG1G1-1/4G141.91-33.253038
G1-1/2-G1-1/4BGJDG1-1/4G1-1/2G1-1/447.80-41.913045
G2-G1-1/2BGJDG1-1/2G2G1-1/259.61-47.803255
G2-1/2-G2BGJDG2G2-1/2G275.18-59.613568
G3-G2-1/2BGJDG2-1/2G3G2-1/287.88-75.183680
G4-G3BGJDG3G4G3113.03-87.883698

Need a size that is not shown? Send us the cable diameter and entry thread.

Selection checks

Choose the right size and construction

Measure the cable diameter and identify the enclosure thread. These details determine which gland will fit.

  1. Required stainless-steel gradeSpecify the steel grade required by your project; the body grade should appear on the drawing or quotation.
  2. Cable and thread dimensionsMatch the cable outside diameter and the enclosure thread to the same gland size.
  3. Corrosion and cleaning exposureChoose body and seal materials for the chemicals, temperature and cleaning process at the installation.

Product support

Need help choosing a cable gland?

Send a model name, a photo or a short question. We can help with sizes, samples and a quotation. If you have them, the details below help us narrow down the options.

Request product support
  • CableOutside diameter and cable type, if known.
  • Armour or screenA cable cross-section photo can help identify the construction.
  • Equipment entryThread marking, hole size or an entry drawing.
  • Body and sealTell us if your project specifies a material.
  • InstallationDescribe where the gland will be used and any heat, water or chemical exposure.
  • Project requirementsInclude any required standard or certificate reference.
  • Model or photoStart with a model number, a photo or a short question.

Stainless Steel Cable Glands FAQ

Cable gland questions

Find answers about fit, assembly and product differences.

Stainless Steel Cable Glands

01How do I specify the stainless-steel grade?

Include the grade required by your project when you enquire. The material callout on the drawing or quotation should identify the grade supplied; a stainless-steel product name does not identify it.

02Does the stainless-steel body determine chemical resistance?

The body is only part of the assembly. The cable seal, O-ring and any washers also contact the surrounding environment. Choose these materials for the chemicals, concentration, temperature and cleaning method involved.

Stainless-Steel Cable Gland — Metric, PG, G and NPT

Stainless-Steel Cable Gland — Metric, PG, G and NPT

01Which stainless-steel grade is used?

304 and 316L versions are available, with EPDM or silicone sealing parts. Choose the material combination for the chemicals and cleaning conditions at the installation.

02How do I choose the thread and cable range?

Match the enclosure thread and the measured cable outside diameter in the same model row. For example, SSM8 lists an M8×1 entry and a 2–5 mm cable range.

03Are locknuts included with NPT versions?

NPT versions are supplied without a locknut as standard. A locknut can be requested separately.

304 Stainless Steel Waterproof Breathable Cable Gland

304 Stainless Steel Waterproof Breathable Cable Gland

01How do I choose the M12×1.5 version?

The two 4–8 mm cable versions have different airflow, thread length and spanner size. Compare the complete row before ordering.

02What pressure is used for the airflow figures?

Airflow is specified at a pressure difference of 70 mbar.

M-NW Female-Thread Cable Gland for Threaded Conduit

M-NW Female-Thread Cable Gland for Threaded Conduit

01Which end connects to the threaded conduit?

The internal-thread connection receives the matching male-threaded conduit or fitting. The cable-side seal is selected from the cable outside diameter.

02Is M-NW interchangeable with M-NLW?

They are separate model series. Use the specified connection form and installation dimensions for the requested series rather than substituting one from its name alone.

M-NLW Internal-Thread Cable Gland

M-NLW Internal-Thread Cable Gland

01How does a female-thread gland differ from an ordinary male-thread gland?

Its internal-thread connection joins a matching male thread. An ordinary male-thread gland connects to a female-threaded opening or passes through a panel with a locknut.

02Which dimensions matter at the mating entry?

Thread standard, nominal size and usable engagement must match the male end. Cable diameter remains a separate measurement at the sealing end.

M-LBK Double-Flare Cable Gland

M-LBK Double-Flare Cable Gland

01Does the double-flare shape establish a vibration rating?

No. The shape identifies the construction; vibration and cable-retention performance need evidence for the selected model and cable.

02How do I identify the correct M-LBK size?

Use the M-LBK model code with the cable outside diameter and the entry dimensions. The complete thread designation is needed when placing an order.

MG-Series EMC Cable Gland

MG-Series EMC Cable Gland

01What distinguishes MG EMC from the ordinary MG gland?

The EMC construction adds contact to the cable screen. The ordinary MG gland provides the cable-entry and sealing construction without that screen-contact function.

02Is cable outside diameter enough to choose an EMC gland?

No. The screen construction and contact diameter also matter. Cable-jacket diameter identifies the sealing range, while the exposed screen must fit the contact arrangement.

Spring-Contact EMC Cable Gland

Spring-Contact EMC Cable Gland

01How is the screen contacted in this gland?

A spring contacts the exposed cable screen inside the gland. The screen preparation and contact diameter must suit that spring.

02Does the screen contact replace cable sealing?

No. The spring makes the electrical contact; the NBR sealing parts act around the cable. Both interfaces must fit the selected cable.

D-Series EMC Cable Gland

D-Series EMC Cable Gland

01Can a D-series gland replace a spring-contact EMC gland?

Not from the EMC label alone. The screen-contact construction, cable preparation and mounting dimensions must match the installation.

02What cable information identifies a D-series size?

Provide the jacket outside diameter and the screen construction and diameter. These describe the separate sealing and screen-contact interfaces.

F-Series EMC Cable Gland for Metric Entries

F-Series EMC Cable Gland for Metric Entries

01What thread system does the F series use?

The F-series gland uses Metric threads. PG, G and NPT versions belong to other constructions in the EMC range.

02Does choosing an EMC gland guarantee the equipment’s shielding performance?

No. The cable screen, contact arrangement and enclosure bonding form one system. The gland provides the screen-contact component within that system.

03Which F-series dimensions are available for selection?

The table gives the entry thread, cable range and wrench dimensions. Request the current drawing for thread length and overall height before machining the enclosure.

Ex-VI Clamping Gland for Unarmoured Cable

Ex-VI Clamping Gland for Unarmoured Cable

01Does Ex-VI require armour or braid on the cable?

No. This construction is for unarmoured cable. A separate armour-clamping gland is needed when the cable armour must be retained at the entry.

02What distinguishes a complete Ex-VI specification?

It includes the cable diameter, entry thread, body and seal materials. Hazardous-area service also requires the certificate and marking for that exact combination.

Ex-VIG Clamping Gland for Unarmoured Cable

Ex-VIG Clamping Gland for Unarmoured Cable

01Can Ex-VIG be substituted for Ex-VI?

The similar names do not establish interchangeability. The cable range, mounting dimensions, sealing configuration and applicable certificate must match the installation.

02How should the stainless-steel option be specified?

Include the required 304 or 316 body grade with the Ex-VIG model and seal material. The grade applies to the selected body option, not automatically to every component.

Ex-VIIIG Single-Seal Armoured Cable Gland

Ex-VIIIG Single-Seal Armoured Cable Gland

01What is the difference between Ex-VIIIG and Ex-VIIG?

Ex-VIIIG is the single-seal version. Ex-VIIG uses double sealing. The required cable layers and sealing dimensions must be matched to the chosen construction.

02Can it be chosen only from the armour type?

No. Wire, braid or tape armour identifies the construction family, but the armour diameter and cable sealing dimensions identify the size.

03Does the model name establish the permitted zone?

No. Zone and protection requirements must be matched to the current certificate for the exact model and configuration.

04How do I select an Ex-VIIIG size?

Compare the cable range, maximum outlet diameter and entry thread. For example, Ex-VIIIGM20D has a 9–20 mm cable range and a 16 mm maximum outlet.

Ex-VIIG Double-Seal Armoured Cable Gland

Ex-VIIG Double-Seal Armoured Cable Gland

01Why does double sealing need more cable measurements?

Each sealing interface must fit the cable layer it contacts. Armour-clamping dimensions remain a separate part of the size selection.

02Is Ex-VIIG the same as Ex-VIIIG?

No. Ex-VIIG is the double-seal model, while Ex-VIIIG is the single-seal model. Keep the complete model designation with the dimensional and certificate requirements.

03How do I select an Ex-VIIG size?

Compare the cable range, maximum outlet diameter and entry thread. For example, Ex-VIIGM20D has a 9–20 mm cable range and a 16 mm maximum outlet.

Ex-BG Clamping Gland for Unarmoured Cable

Ex-BG Clamping Gland for Unarmoured Cable

01Is Ex-BG an alternative name for Ex-B?

They are separate model designations. A replacement needs the correct cable range, mounting dimensions and sealing arrangement, together with the applicable certificate.

02What should an Ex-BG enquiry identify?

Include the entry thread and cable outside diameter, then name the body and seal material required. For a hazardous location, include the equipment protection marking so the certificate scope can be matched.

BDM-BDT / Ex-BDT Threaded Stopping Plug

BDM-BDT / Ex-BDT Threaded Stopping Plug

01How is a stopping plug sized?

Match the complete entry thread and available engagement. Cable diameter is not a sizing dimension for a solid stopping plug.

02Can a general-purpose plug replace Ex-BDT?

For hazardous-area equipment, the replacement plug needs the appropriate certificate and installation conditions for that equipment. A matching thread alone is not sufficient.

BGJ-A Female-to-Female Pipe Coupler

BGJ-A Female-to-Female Pipe Coupler

01Does BGJ-A clamp or seal a cable jacket?

No. It is a threaded pipe coupler. Its two mating thread designations and engagement dimensions identify the connection.

02What information is needed for a reducing coupler?

Give the thread standard and size at each end, along with the required overall length. For hazardous-area equipment, the chosen coupler also needs the matching approval scope.

BGJ-B Thread Adapter — Reducer and Enlarger

BGJ-B Thread Adapter — Reducer and Enlarger

01What identifies a BGJ-B adapter?

Specify both mating thread designations and the required connection direction. One nominal size does not fully describe a reducer or enlarger.

02Can an adapter preserve hazardous-area approval automatically?

No. An adapter used on hazardous-area equipment must be permitted by the equipment and adapter certificates and their installation conditions.

BGJ-C Male-to-Male Reducing Nipple

BGJ-C Male-to-Male Reducing Nipple

01How does BGJ-C differ from BGJ-A?

BGJ-C has male threads at both ends. BGJ-A has female threads at both ends; they connect to opposite mating-thread forms.

02What dimensions are needed to order a reducing nipple?

State the full thread designation at each end, required engagement and overall length. Hazardous-area installations also need the certificate for the selected configuration.

BGJ-D Male-to-Female Reducing Bushing

BGJ-D Male-to-Female Reducing Bushing

01Which thread size goes first when describing a bushing?

Identify the outer male thread and inner female thread explicitly. For example, the Metric table includes an M20×1.5 male to M16×1.5 female reduction.

02Is a reducing bushing the same as a pipe coupler?

No. A bushing nests a smaller female connection inside a larger male thread. A coupler joins connections through two ends. Any hazardous-area use needs approval for the selected fitting.